(1) Safety
· The switchgear is equipped with comprehensive mechanical interlocking and electrical interlocking functions.
The enclosure and cable compartment design meets the 20 kA/1s arc-fault requirement.
· The enclosure has good grounding continuity.
(2) Reliable
· The stainless steel gas tank boasts an IP67 protection rating and requires no refilling or maintenance throughout its service life.
· The air box design strength meets the requirements for altitudes of 5,000 m and below.
· The operating mechanism meets the 720-hour salt spray test requirement.
(3) Anti-fouling and moisture-proof
· Suitable for operation in environments with industrial pollution, salt content, and high humidity.
· Corrosion protection rating for switchgear: Onshore—C4; Offshore—C4H
· All connections between secondary components use moisture-proof, damp-proof, and mold-resistant connectors.
(3) Smart Management
· Provide intelligent solutions to facilitate digital upgrades.
· Provides online monitoring functions for selectable switch states, mechanical characteristics, vacuum status, temperature, and partial discharge.
· Supports remote operation, monitoring, and management
· The installation and user manual can be obtained via a QR code.
Altitude: <5000m (When the operating altitude of the equipment exceeds 2000m, this must be specifically noted);
Ambient temperature: Maximum temperature +50℃, minimum temperature -50℃, average value within 24 hours ≤35℃;
Environmental humidity: Average relative humidity over 24 hours <95%; monthly average relative humidity ≤90%.
Electromagnetic interference: The amplitude of electromagnetic interference induced in the secondary system ≤ 1.6 kV;
Installation environment: The surrounding air contains no explosive or corrosive gases, and the installation location is free from frequent, severe vibrations or shocks.
Note: If the operating environment conditions exceed those specified above, please consult our company to discuss custom solutions.
IEC62271-1:2017 and GB/T11022-2020—Common Technical Requirements for High-Voltage Switchgear and Control Equipment
IEC62271-200:2011 and GB/T3906-2020 3.6kV~40.5kV AC metal-enclosed switchgear and control equipment
IEC62271-100:2017 and GB/T1984-2014 AC High-Voltage Circuit Breakers
IEC62271-105:2021 and GB/T16926-2009 AC High-Voltage Load Break Switch-Fuse Combination Apparatus
IEC 16271-102:2001 + A1:2011 and GB/T 1985-2014 High-voltage AC isolating switches and earthing switches
IEC60529 and GB/T4208-2017: Enclosure Protection Ratings (IP Codes)
GB/T11023-2018 Test Method for Gas Sealing of Sulfur Hexafluoride in High-Voltage Switchgear
DL/T402-2016 Technical Specifications for Ordering High-Voltage AC Circuit Breakers
DL/T486-2021 Technical Specifications for Ordering High-Voltage AC Disconnect Switches and Earthing Switches
DL/T403-2017 Technical Specifications for Ordering 12kV~40.5kV High-Voltage Vacuum Circuit Breakers
DL/T404-2018 3.6kV~40.5kV AC Metal-Enclosed Switchgear and Control Equipment
DL/T593-2016 Common Technical Requirements for Standards of High-Voltage Switchgear and Control Equipment
Qian Gu Electric is committed to environmental protection. Its products are certified under the ISO 14001 international environmental management system and strictly adhere to this standard.
Recycling and Disposal
The design and manufacture of UN3 series switchgear comply with the requirements of the national standard GB/T 3906 and the international standard IEC 62271-200. At the end of the product’s lifecycle, SF6 gas will be recovered and reused in accordance with relevant standards.
Sustainable development
The UN3 series switchgear continuously reduces the use of SF6 during manufacturing and does not use SF6 gas during installation.
The product is made from reusable materials.
Provide self-powered relays and devices to avoid additional energy consumption.
1. Side-mounted main busbar: Rated current meets 1250A and 2500A.
2. Independent busbar room: Meets the requirements for either a single gas-insulated switchgear (GIS) bay or a double GIS bay.
3. Three-position isolating switch and mechanism: can be operated manually or electrically.
4. Circuit Breaker and Mechanism: The circuit breaker is equipped with a spring-operated mechanism and features automatic reclosing functionality. It can be manually or electrically energized.
5. Installation of Cable Accessories and Surge Arresters: C-type bushings—choose either 1 set of cable + surge arrester or 2 sets of cable + surge arrester.
6. Cable Room: Meets installation requirements for cables of various specifications.
7. Cable Room Pressure Relief Channel
8. Air box pressure relief channel
9. Circuit Breaker Room
10. Compartment bushing
11. Nameplate
12. Simulated busbar
13. Protective device

|
Operating continuity levels defined in GB/T 3906 |
||||
|
Other high-voltage compartments or functional units remain energized. |
LSC 1: Low service continuity |
|
LSC 1 | LSC 2 |
|
LSC 2: Higher Service Continuity |
|
|
● | |
|
Partition between compartments |
PI: Insulating partition |
|
PI |
PM |
|
PM: Metal Grounding Baffle |
|
|
● | |
|
Insulation and Switching |
||||
|
Main circuit disconnection |
|
|
Vacuum circuit breaker |
|
|
Working principle |
|
|
Three-position load switch |
|
|
Interrupting medium |
|
|
Vacuum arc-extinguishing chamber |
|
|
Insulating medium |
|
|
SF6 gas |
|
|
Relative inflation pressure |
Rated inflation pressure (gauge pressure at 20℃) |
MPa |
0.04 |
|
|
Minimum inflation pressure (gauge pressure at 20℃) |
MPa |
0.02 |
||
|
Annual relative leakage rate of gas |
|
%/year |
≤0.01 |
|
|
Insulation level |
||||
|
Rated voltage |
|
kV |
40.5 |
|
|
Rated frequency |
|
Hertz |
50 |
|
|
Rated insulation level |
Power-frequency withstand voltage (phase-to-phase, phase-to-ground, vacuum interrupter contacts) |
kV |
95 |
|
|
Power-frequency withstand voltage (isolated break) |
kV |
118 |
||
|
Power-frequency withstand voltage (auxiliary and control circuits) |
kV |
2 |
||
|
Lightning impulse withstand voltage (phase-to-phase, phase-to-ground, vacuum interrupter) |
kV |
185 |
||
|
Lightning Impulse Withstand Voltage (Isolation Break) |
kV |
215 |
||
|
Current level |
||||
|
Rated current—busbar |
A |
1250/2500 |
||
|
Rated short-circuit breaking current |
kA |
31.5 |
||
|
Rated short-circuit making current (main switch/grounding switch) |
kA |
80/80 |
||
|
Short-time withstand current and duration (main circuit + earthing switch, earthing connection) |
kA/s |
31.5/4/27.4/2 |
||
|
Rated peak withstand current (main circuit + earthing switch, earthing connection) |
kA |
80/68 |
||
|
Internal arc fault withstand capability |
||||
|
Grade A |
A FL front and side views |
kA |
31.5 |
|
|
AFLR front, side, and rear |
kA |
31.5 | ||
|
Duration |
S |
0.5 |
||
|
Enclosure protection rating |
||||
|
Complies with GB/T4208 standard enclosure protection. |
An energized electrical box |
|
IP67 |
|
|
Cable Room |
|
IP43 |
||
|
Institutional Room |
|
IP4X |
||
|
Low-pressure room |
|
IP4X |
||
|
Mechanical impact protection rating |
||||
|
Grade compliant with GB/T 20138 |
|
IK07 | ||
|
Other features |
||||
|
Expected service life |
Year |
30 |
||
|
Busbar/Grounding Busbar (Copper Bar) |
|
300 mm² |
||