UN3W Outdoor Switchgear and Cable Junction Box

UN3W Outdoor Switchgear and Cable Junction Box

The UN3W-12, 24, and 40.5kV outdoor switchgear cubicles (cable distribution boxes) are a new type of modular, functionally integrated, highly reliable, compact, and maintenance-free switchgear cubicle (cable distribution box). They are suitable for power supply lines with voltage levels of 40.5kV and below, and serve the functions of cable branching, disconnection, control, and protection.

Product Features


The enclosure is welded from stainless steel, and all sheet-metal joints feature a waterproof sealing design.
Optional fully insulated SF6 load switch solution, equipped with touchable shielded T-type cable accessories and surge arresters. Each ring main unit line can be fitted with a load switch, allowing any branch circuit to be freely disconnected or put into operation at any time. Other rings…

The network circuit is unaffected.
(1) Anti-fouling and moisture-proof
The roof, side panels, and doors of the outdoor switchgear cabinet (cable distribution box) feature a rainproof structural design.
Suitable for operation in environments with industrial pollutants, salt content, and high humidity.
Outdoor cubicle switchgear (cable distribution box): Corrosion protection rating—onshore: C4; offshore: C4H.
(2) Ground continuity
The primary circuit and secondary circuit grounding are connected separately to the grounding grid.
The enclosure of outdoor switchgear cabinets (cable distribution boxes), as well as touchable doors and side panels, feature good grounding continuity, effectively ensuring personnel safety.

Operating Environment Conditions


Altitude: S ≤ 5,000 m (Please specify explicitly if the device is operated at an altitude exceeding 2,000 m);
Ambient temperature: Maximum temperature +50℃, minimum temperature -50℃, average value over 24 hours: 35°C.
Environmental humidity: The 24-hour average relative humidity is 95%; the monthly average relative humidity is 90%.
Electromagnetic interference: The amplitude of electromagnetic interference induced in the secondary system is 1.6 kV;
Installation environment: The surrounding air contains no explosive or corrosive gases, and the installation location is free from frequent, severe vibrations or shocks.
Note: If the operating environment conditions exceed those specified above, please consult our company to arrange a customized solution.

Applicable Standards


GB/T 3906-2020 3.6kV~40.5kV AC Metal-Enclosed Switchgear and Control Equipment
GB/T 11022-2020 Common Technical Requirements for High-Voltage Switchgear and Control Equipment (IEC 62271-1:2007 MOD)
JB/T10840-2019 3.6kV~40.5kV High-Voltage AC Metal-Enclosed Cable Tap Switchgear
GB11033.2-1989 Basic Technical Requirements for Power Cable Accessories Rated 26/35 kV and Below
GB/T17467-2020 High-Voltage/Low-Voltage Prefabricated Substation

Recycling and Reuse


Qian Gu Electric is committed to environmental protection. Its products are certified under the ISO 14001 international environmental management system and strictly adhere to this standard.
Recycling and Disposal
The design and manufacture of UN3W switchgear (branch boxes) comply with the requirements of the national standard JB/T10840. At the end of the product’s lifecycle, they will be recycled and reused in accordance with relevant standards.
Sustainable development
The installation process does not use SE6 gas: all products are made from 100% recyclable materials; self-powered relays and devices are provided to avoid additional energy consumption.

Structural Diagram


Unifortune

Technical Specifications


The operational continuity levels defined in GB/T 17467

Other high-voltage compartments or functional units remain energized.

LSC 1: Lower service continuity

LSC 1

LSC 2

LSC 2: Higher Service Continuity

●

Partition between compartments

PI: Insulating partition

PI PM

PM: Metal Grounding Baffle

●

Insulation level

12 24 40.5

Rated voltage

kV

12

24

40.5

Rated frequency

Hertz

50

50

50

Rated insulation level

Power-frequency withstand voltage (phase-to-phase, phase-to-ground, vacuum interrupter contacts)

kV

42

65

95

Power-frequency withstand voltage (isolated break)

kV

48

79

118

Power-frequency withstand voltage (auxiliary and control circuits)

kV

2

2

2

Lightning impulse withstand voltage (phase-to-phase, phase-to-ground, vacuum interrupter)

kV

75

125

185

Lightning Impulse Withstand Voltage (Isolation Break)

kV

85

145

215

Current level

12

24

40.5

Rated current—busbar

kA

630

630

630

Rated short-circuit breaking current

kA

25

25

25

Rated short-circuit making current (main switch/grounding switch)

kA

63/63

63/63

63/63

Short-time withstand current and duration (main circuit + earthing switch, earthing connection)

kA/s

25/17.6

25/17.6

25/17.6

Rated peak withstand current (main circuit + earthing switch, earthing connection)

kA

63/54

63/54

63/54

Internal arc fault withstand capability

Grade B

B FL Front and side

kA

20

B FLR Front, side, and rear

kA

20

Duration

S

1

Enclosure protection rating

Enclosure protection conforming to GB/T 4208 standard

An energized electrical box

IP67

Cable Room

IP43

Institutional Room

IP4X

Low-pressure room

IP4X

Mechanical impact protection rating

Grade compliant with GB/T 20138

IK07

Other features

Expected service life

Year

30

Busbar/Grounding busbar (copper bar)

300mm2

Model Description


Model Specifications

Rated Voltage (kV)

Rated Voltage (A) Cable cross-section (mm²) 2)
Minimum value (mm) Maximum value (mm)

SLKCTH-33/□/□

36

630 (1250)

35

630

SLKCTH-35/□/□

40.5

630(1250)

35

630

Correspondence Table Between Stress Cone Inner Hole and Cable


Inner hole of stress cone

Diameter Specification (mm)

Cable core insulation diameter range

19/33 (36) kV

26/35 (40.5) kV 20.8/36 (42) kV
Minimum value (mm) Maximum value (mm) Cable cross-section (mm²) 2) Cable cross-section (mm²) 2) Cable cross-section (mm²) 2)

Φ19

  Φ22

Φ24

25-50

Φ23

  Φ25

Phi  29.5

35-95

25-35

25-50

  Φ26

Φ30

Φ35

120-185

50-70

70-120

  Φ30

  Φ35

  Φ38

240-300

95-120

150-185

  Φ34

  Φ38

  Φ42

400

150-240

240-300

  Φ38

Phi  44

  Φ48

500-630

300-400

400-500

  Φ42

  Φ49

Phi 54

800

500-630

630

Model Description: SLK1250T-51/134


Model

Name

SLK1250T-51/134

Other custom models

System Nominal Voltage (kV)

35

Rated Voltage (kV)

51

Continuous operating voltage (kV)

40.8

Residual voltage under lightning impulse current (kV)

≤134

Voltage U1mA at 1mA DC ≥ (kV)

73

Leakage current at 0.75U1mA ≤ (μA)

50

2ms Square Wave Impact Capacity (A)

600

Power-frequency withstand voltage of composite insulation jacket (kV/5 min)

95

Partial discharge (≤10 pC) corresponding voltage

45

 ;