Indoor AC Vacuum Circuit Breaker (with Isolation)

Indoor AC Vacuum Circuit Breaker (with Isolation)

The UN5-40.5(G)-T1250A-31.5kA series indoor vacuum circuit breakers with isolation are suitable for transmission networks of wind and photovoltaic generators operating at 50 Hz, 3-phase AC, with a rated voltage of 40.5 kV. They can interrupt load currents, overload currents, and short-circuit currents. Specifically designed for 35 kV packaged substations, these circuit breakers can also be used as standalone electrical units in power systems (installed in switchgear cabinets or wall-mounted), and are compatible with distribution equipment, ring main units, or combined substations.

Product Features


The arc-extinguishing chamber employs a vacuum interrupter, and the vacuum arc-extinguishing chamber is encapsulated in epoxy resin to form a solid-insulated pole. The wall-through solid-insulated pole is installed horizontally. The moving end of the pole is connected to the outgoing terminal via a flexible connection, while the stationary end of the pole is linked to the pivot point of the disconnecting switch’s moving blade. This arrangement effectively separates the disconnecting switch and the earthing switch into two independent compartments, ensuring that the circuit breaker can be safely maintained even when de-energized. This product features a novel design, a compact structure, long service life, reliable operation, small size, convenient operation and maintenance, and high safety.
1. The product components feature modular design, and the cabinet’s “five-protection” system is simple, reliable, and consistent.
2. The arc-extinguishing chamber circuit is encapsulated using high-quality epoxy resin material. The partial discharge level of each encapsulated pole is ≤5 pC (at 45 kV), enhancing the circuit breaker’s adaptability and reliability in harsh environments and ensuring maintenance-free operation throughout its service life.
3. The integrated design of the isolating switch, circuit breaker switch, and grounding switch results in a high-voltage vacuum circuit breaker with a clearly visible isolation gap.
4. The panel features a single-line analog marking design that is simple and easy to understand, helping to prevent accidental operation.
5. A current transformer can be installed on the outgoing side of the switchgear, allowing for a smaller cabinet or packaged substation size.
6. It can be equipped with a smart online monitoring unit and diagnostic system; the operating status of the switch can be remotely accessed via a communication module.

Safety Design


The indoor high-voltage AC vacuum circuit breaker with isolation features is equipped with sophisticated mechanical and electrical interlocking devices, ensuring exceptionally high operational reliability and a long service life. When paired with the corresponding outdoor switchgear, it can reliably perform safe power distribution functions, thereby guaranteeing the safety of both operators and equipment.

Operating Environment Conditions


Altitude: ≤5000m (When the operating altitude of the equipment exceeds 2000m, this must be specifically noted);
Ambient temperature: Maximum temperature +50℃, minimum temperature -50℃, average value within 24 hours ≤35℃;
Environmental humidity: Average relative humidity over 24 hours ≤ 95%; average monthly relative humidity ≤ 90%.
Electromagnetic interference: The amplitude of electromagnetic interference induced in the secondary system ≤ 1.6 kV;
Installation environment: The surrounding air contains neither explosive nor corrosive gases, and the installation location is free from frequent, severe vibrations or shocks.
Note: If the operating environment conditions exceed those specified above, please consult our company to arrange a customized solution.

 

Applicable Standards


· Common technical requirements shared by IEC62271-1:2017 and GB/T11022-2020—Standard for High-Voltage Switchgear and Control Equipment
· IEC62271-200:2011 and GB/T3906-2020 3.6 kV to 40.5 kV AC metal-enclosed switchgear and control equipment
· IEC 62271-100:2017 and GB/T 1984-2014 AC High-Voltage Circuit Breakers
· IEC62271-105:2021 and GB/T16926-2009 AC High-Voltage Load Break Switch-Fuse Combination Apparatus
· IEC16271-102:2001+A1:2011 and GB/T1985-2014 High-voltage AC isolating switches and earthing switches
· IEC60529 and GB/T4208-2017: Enclosure Protection Ratings (IP Codes)
· GB/T11023-2018 Test Method for Gas Sealing of Sulfur Hexafluoride in High-Voltage Switchgear
· DL/T402-2016 Technical Specifications for Ordering High-Voltage AC Circuit Breakers
· DL/T486-2021 Technical Specifications for Ordering High-Voltage AC Disconnect Switches and Earthing Switches
· DL/T403-2017 Technical Specifications for Ordering 12kV~40.5kV High-Voltage Vacuum Circuit Breakers
· DL/T404-2018 3.6 kV to 40.5 kV AC Metal-Enclosed Switchgear and Control Equipment
· DL/T593-2016 Common Technical Requirements for Standards of High-Voltage Switchgear and Control Equipment

Product Technical Specifications


Implementation standard GB/T 1984

Insulation level

Rated voltage

KV

40.5

Rated frequency

Hertz

50

Rated insulation level

Power-frequency withstand voltage (phase-to-phase, phase-to-ground, vacuum interrupter contacts)

KV

95

Power-frequency withstand voltage (isolated break)

KV

118

Power-frequency withstand voltage (auxiliary and control circuits)

KV

2

Lightning impulse withstand voltage (phase-to-phase, phase-to-ground, vacuum interrupter)

KV

185

Lightning Impulse Withstand Voltage (Isolation Break)

KV

215

Current level

Rated current

A

630, 1250

Rated short-time withstand current

KA

25, 31.5

Duration

S

4

Rated peak withstand current

KA

63, 80

Rated short-circuit breaking current

Fault protection

KA

25, 31.5

Rated short-circuit making current

Short-circuit closing

KA

63, 80

Action time

Trip time

S

<60ms

Closing time

S

<45ms

Circuit breaker life (GB/T 1984)

Mechanical life

M1: 2000 times

M1

M2

M2: 10,000 times

●

Electrical life

E1

E1

E2

E2

●

Operation Sequence (Auto Reclosing)

Operation Sequence

There is

Fault trip

Manual trip release

There is

Fast switching

Electrically operated trip/release mechanism

Auto-reclosing

0-0.3s-C0-180s-C0

Manual

There is

Electrical/Remote Operation

Optional

Closing speed

m/s

1.4–2.0

Trip speed

m/s

0.8~1.2

Closing time (rated voltage)

m/s

30~70

Trip time (rated voltage)

m/s

20~50

Circuit resistance

microohm

≤80

Switch Performance Parameters


Serial number

Name

Unit

Data

1

Rated voltage

KV

40.5

2

1-minute power frequency withstand voltage (RMS value)

KV

95

3

Lightning impulse withstand voltage (peak)

KV

185

4

Rated frequency

Hertz

50

5

Rated current

A

1250/1600/2000/2500

6

Rated short-time withstand current

KA

20/25/31.5

7

Rated peak withstand current

KA

50/63/80

8

Rated short-circuit duration

s

4

9

Rated short-circuit breaking current

KA

20/25/31.5

10

Rated short-circuit making current

KA

50/63/80

11

Rated operating sequence

O-0.3s-CO-180s-CO

12

Break time

Ms.

<80

13

Rated short-circuit breaking current number of breaking operations

Next

20

14

Single capacitor bank breaking current

A

630

15

Breaking current of back-to-back capacitor banks

A

400

16

Rated operating voltage

V

AC/DC 110, 220

17

Mechanical life

Next

10000