Outdoor Box-Type Switchgear (Cable Branching Box)

Outdoor Box-Type Switchgear (Cable Branching Box)

The enclosure shell can be made from a variety of materials, offering sufficient mechanical strength. The color of the enclosure shell is coordinated with the surrounding environment. The slope of the box’s top cover shall be no less than 3 degrees, and a rainproof eave shall be installed. A louvered vent shall be provided at the inner top of the box to ensure natural ventilation. The bottom of the enclosure is effectively sealed to prevent small animals from entering the enclosure through the cable trench. The enclosure is equipped with a dedicated grounding conductor connected to the grounding grid. The enclosure houses UN3 series switchgear.

Product Features


The enclosure is welded from stainless steel, and all sheet-metal joints feature a waterproof sealing design, achieving an IP55 protection rating.
Optional fully insulated SF6 load switch solution, equipped with touchable shielded T-type cable accessories and surge arresters. Each ring network line can be fitted with a load switch, allowing any branch circuit to be freely disconnected or put into operation without affecting other ring network circuits.

Applicable Locations


UN3W-12, 24, and 40.5kV outdoor switchgear cabinets (cable tap boxes) are a new type of modular, multi-functional, highly reliable, compact, and maintenance-free switchgear cabinet (cable tap box). They are suitable for power supply lines with voltage levels of 40.5kV and below, and serve the functions of cable tapping, disconnection, control, and protection.

Operating Environment Conditions


Altitude: ≤5000m (When the operating altitude of the equipment exceeds 2000m, this must be specifically noted);
Ambient temperature: Maximum temperature +50℃, minimum temperature -50℃, average value within 24 hours ≤35℃;
Environmental humidity: Average relative humidity over 24 hours ≤ 95%; average monthly relative humidity ≤ 90%.
Electromagnetic interference: The amplitude of electromagnetic interference induced in the secondary system ≤ 1.6 kV;
Installation environment: The surrounding air contains neither explosive nor corrosive gases, and the installation location is free from frequent, severe vibrations or impacts.
Note: If the operating environment conditions exceed those specified above, please consult our company to discuss custom solutions.

 

Applicable Standards


GB/T 3906-2020 3.6kV~40.5kV AC Metal-Enclosed Switchgear and Control Equipment
GB/T11022-2020 — Common Technical Requirements for High-Voltage Switchgear and Control Equipment (IEC 62271-1:2007 MOD)
JB/T10840-2019 3.6 kV ~ 40.5 kV High-Voltage AC Metal-Enclosed Cable Tap Switchgear
GB11033.2-1989 Basic Technical Requirements for Power Cable Accessories Rated 26/35 kV and Below GB/T17467-2020 Prefabricated Substations for High-Voltage/Low-Voltage Applications

Recycling and Reuse


Qian Gu Electric is committed to environmental protection. Its products have been certified under the 15014001 international environmental management system and strictly adhere to this standard.
Recycling and Disposal
The design and manufacture of UN3W switchgear (branch boxes) comply with the requirements of the national standard GB/T10840. At the end of the product’s lifecycle, they will be recycled and reused in accordance with relevant standards.
Sustainable development
During the manufacturing process, the UN3W switchgear (branching box) continuously reduces the use of 5F6, and no 5F6 gas is used during installation.

All products are made from 100% recyclable materials.
Provide self-powered relays and devices to avoid additional energy consumption.

Technical Specifications


Operating continuity levels defined in GB/T17467
Other high-voltage compartments or functional units remain energized. LSC 1: Lower service continuity   LSC1 LSC 2
LSC 2: Higher Service Continuity   ●
Partition between compartments PI: Insulating partition   PI PM
PM: Metal Grounding Baffle   ●
Insulation level 12 24 40.5
Rated voltage   kV 12 24 40.5
Rated frequency   Hertz 50 50 50
 

 

Rated insulation level

Power-frequency withstand voltage (phase-to-phase, phase-to-ground, vacuum interrupter) kV 42 65 95
Power-frequency withstand voltage (isolated break) kV 48 79 118
Power-frequency withstand voltage (auxiliary and control circuits) kV 2 2 2
Lightning impulse withstand voltage (phase-to-phase, phase-to-ground, vacuum interrupter) kV 75 125 185
Lightning Impulse Withstand Voltage (Isolation Break) kV 85 145 215
Current level 12 24 40.5
Rated current—busbar A 630 630 630
Rated short-circuit breaking current kA 25 25 25
Rated short-circuit making current (main switch/grounding switch) kA 63/63 63/63 63/63
Short-time withstand current and duration (main circuit + earthing switch, earthing connection) kA/s 25/17.6 25/17.6 25/17.6
Rated peak withstand current (main circuit + earthing switch, earthing connection) kA 63/54 63/54 63/54
Internal arc fault withstand capability
Grade B B FLR front side and rear kA 20
Duration S 1
Enclosure protection class
 

 

Enclosure protection conforming to GB/T 4208 standard

An energized electrical box   IP67
Cable Room   IP43
Institutional Room   IP4X
Low-pressure room   IP4X
Mechanical impact protection rating
Grade compliant with GB/T 20138   IK07
Other features
Expected service life Year 30
Busbar/Grounding busbar (copper bar)   120 mm²